This attic ventilation calculator sizes required net free area (NFA) for your attic by the building-code 1/150 rule (and the 1/300 exception), split evenly between soffit intake and ridge/roof exhaust.

Total NFA required –
Intake (soffit) — 50% –
Exhaust (ridge/roof) — 50% –
Ridge vent length at 18 sq in NFA/ft –

NFA is the vent’s actual open area after screens and louvers — a “100 sq in” louvered vent often nets half that. Buy by the NFA printed on the product, never by the hole size, and keep intake ≥ exhaust so the attic draws from soffits rather than from your living space.

Hot, Wet Attic Air Is a Roof Killer — Ventilation Is the Drain

The other half of attic performance is our Insulation Calculator. Part of our Construction Calculators collection.

Worked Example (Verified)

  • 1,200 sq ft attic, 1/150 rule (defaults): total NFA = 8.00 sq ft = 1,152 sq in → 576 sq in intake + 576 exhaust; as ridge vent at 18 sq in/ft that’s 32 linear ft of ridge — a number most 1960s gable-vent houses miss by half
  • The 1/300 path (ceiling vapor barrier + balanced high/low vents, where adopted): halves everything — 576 sq in total; know your jurisdiction before banking the discount
  • Blocked soffits quietly zero the intake side: insulation baffles at every rafter bay are the $2 part that makes the whole system real

Ventilation Discipline

  • Balance matters more than totals: excess exhaust without intake pulls conditioned air (and moisture) from the house through ceiling leaks.
  • Never mix exhaust types at the ridge (ridge vent + powered fan + turbines fight each other, short-circuiting the soffit draw).
  • Bath fans and dryer vents must terminate outside — an attic “vented” by a bath fan is a mold incubator wearing a code costume.
  • Unvented (conditioned) attics are a legitimate modern alternative with foam at the roofline — a different system entirely; don’t half-mix the two philosophies.

Related Tools

Frequently Asked Questions

How much attic ventilation do I need?

Code standard: net free area = attic floor area ÷ 150. A 1,200 sq ft attic needs 8 sq ft (1,152 sq in) of NFA, split evenly between low intake (soffits) and high exhaust (ridge/roof). With a ceiling vapor barrier and balanced vents, many codes allow 1/300 — half as much. This calculator runs both rules.

What is net free area (NFA)?

The actual open area of a vent after its screen, mesh and louvers take their cut — often 50–75% of the vent’s face size. Products are rated in NFA (sq in); always size by that number, and prefer vents with published NFA over ones sold by rough hole dimensions.

Why split intake and exhaust evenly?

Stack-effect flow needs an entrance matched to the exit: soffit air sweeps the underside of the deck and leaves at the ridge. Intake-starved systems pull air from the conditioned house instead (energy loss, moisture transport), while exhaust-starved systems stagnate no matter how big the soffits are.

How many feet of ridge vent do I need?

Divide the exhaust NFA by your product’s NFA per linear foot (a common rating is 18 sq in/ft): the defaults’ 576 sq in exhaust → 32 ft. If your ridge is shorter than the requirement, supplement with roof vents rated in NFA — added, not substituted blindly.

Does attic ventilation really extend roof life?

Yes: summer attic heat (140°F+ unvented) cooks shingles from below and voids some warranties, while winter moisture from the house condenses on cold decking and rots it. Ventilation moderates both — it’s moisture management in winter, heat management in summer.

Is this attic ventilation calculator free?

Yes — free, instant, no sign-up.